Type

NTDH

Short description

NTDH utilizing excess heat for residential park heating

Location

"Sattlerweg" area in Herford

Country

Germany

End users

Residential park (240 residential units)

Heat source

Excess heat

Description

Excess heat (process excess heat at a temperature between 25°C and 35°C from local dairies) heats brine water in HEX; 16 decentralized heat pumps per residential complex which use that brine water for SH and DHW

Cooling

Missing info

Heat source-network connection

HEX

Booster HP or no for SH

HP

Booster HP, IHEU or DHSU for DHW

HP

Category

2.1.1.1.1.

Costs/Price [€] (Investment; Operation; Cost for the consumer)

Price for consumers (without tax): heat-base part (162.00 €/year), variable part (9.00 ct/kWh); DHW- for heating- base part (57.00 €/year), variable part (8.37 €/m3); DHW-portable water- base part (57 €/year), variable part (10.12 €/m3)

Tsource [°C]

30

Tsupply,max [°C] (network)

23

Tsupply,min [°C] (at consumer substation)

35

Tsupply,max [°C] (at consumer substation)

50

SCOP=(reference annual heating demand)/(seasonal electricity consumption for heating) [-]

4.6

Installed capacity [MW]

15 to 105 kW (16 larger HPs per residential complex)

Network length [km] (if not specified-pipes, trench specified)

0.7

Reference 1

https://doi.org/10.1016/j.rser.2018.12.059

Reference 2

https://energieservice-ww.com/wohnpark-sattlerweg-privat.html

Reference 3

https://www.diekaelte.de/sites/default/files/ulmer/file_172029.pdf

Number 12