Type

NTDH

Short description

NTDH utilizing ground water for residential heating

Location

Jardins de la Pâla, Bulle

Country

Switzerland

End users

81 apartments

Heat source

Ground water

Description

Heat is transferred through HE to network; Network supplies HPs for SH and DHW

Cooling

Yes

Heat source-network connection

HEX

Booster HP or no for SH

HP

Booster HP, IHEU or DHSU for DHW

HP

Category

1.4.1.1.1.

Costs/Price [€] (Investment; Operation; Cost for the consumer)

Investment: 3.798 mil. €; Variable heat price 4 ct./kWh and DHW 7 ct./kWh

Tsource [°C]

10.5

Tsupply,min [°C] (network)

8

Tsupply,max [°C] (network)

9

Tsupply,min [°C] (at consumer substation)

35

Tsupply,max [°C] (at consumer substation)

45

Treturn [°C] (network)

4

SCOP=(reference annual heating demand)/(seasonal electricity consumption for heating) [-]

2.7

SEER=(reference annual cooling demand)/(annual electricity consumption for cooling) [-]

12

Installed capacity [MW]

2

Heating demand [MWh/year]

2100

Network length [km] (if not specified-pipes, trench specified)

0.85

Project area [km2]

0.065

LHD (linear heat density)=(total heat demand)/(length of network) [kWh/m/year]

2470.588 (calculated from data)

LHPDD (linear heating power demand density)=(installed thermal power capacity)/(network length(pipes)) [kW/m]

2.4

Reference 1

https://pubdb.bfe.admin.ch/de/publication/download/8836

Reference 2

https://doi.org/10.1016/j.rser.2018.12.059

Reference 3

https://heatpumpingtechnologies.org/annex47/wp-content/uploads/sites/54/2018/12/annex-47sub-projetcsbulle.pdf

Number 22