Type

NTDH

Short description

NTDH utilizing lake water for heating buildings

Location

La Tour-de-Peilz

Country

Switzerland

End users

Around 300 buildings (mostly residential)

Heat source

Lake water

Description

Lake water transfer heat to distribution network through HE; Distribution network is connect to substations with HPs (10 kW to 500 kW) for SH and DHW

Cooling

Yes

Heat source-network connection

HEX

Booster HP or no for SH

HP

Booster HP, IHEU or DHSU for DHW

HP

Category

1.5.1.1.1.

Costs/Price [€] (Investment; Operation; Cost for the consumer)

Investment: 30 mil. €

Tsource [°C]

7

∆Tsource [°C]

4

Tsupply,min [°C] (network)

2

Tsupply,max [°C] (network)

20

Tsupply,min [°C] (at consumer substation)

55

Tsupply,max [°C] (at consumer substation)

60

Treturn [°C] (network)

9

SCOP=(reference annual heating demand)/(seasonal electricity consumption for heating) [-]

3.75

Installed capacity [MW]

10

Heating demand [MWh/year]

18.5

Network length [km] (if not specified-pipes, trench specified)

4.1

LHD (linear heat density)=(total heat demand)/(length of network) [kWh/m/year]

4.512 (calculated from data)

LHPDD (linear heating power demand density)=(installed thermal power capacity)/(network length(pipes)) [kW/m]

2.4

Reference 1

https://pubdb.bfe.admin.ch/de/publication/download/8836

Reference 2

https://doi.org/10.1016/j.rser.2018.12.059

Number 25