Type

LTDH

Short description

LTDH Houses connected to existing DH with low temperature heating usage

Location

Tilst

Country

Denmark

End users

8 existing detached houses with radiators

Heat source

Existing DH

Description

Connected to existing DH, shunt at the beginning of the street to reduce supply temperature-mix of return water from LTDH and MTDH supply; Two ways of connecting main network with substation: direct and indirect (with HEX)

Cooling

Missing info

Heat source-network connection

Shunt

Booster HP or no for SH

No

Booster HP, IHEU or DHSU for DHW

IHEU

Category

3.1.2.1.1.

Tsource [°C]

75

Tsupply,min [°C] (network)

61

Tsupply,max [°C] (network)

66

Tsupply,min [°C] (at consumer substation)

55 (indirect connection)

Tsupply,max [°C] (at consumer substation)

60 (direct connection)

Treturn [°C] (network)

Direct connection return 30; Indirect connection return 30 (primary side) and 25 (secondary side)

Network length [km] (if not specified-pipes, trench specified)

0.23 (trench)

Heat loss [%]

17.5

Reference 1

https://www.danskfjernvarme.dk/-/media/danskfjernvarme/gronenergi/projekter/eudp-lavtemperatur-fjv/guidelines-for-LTDH inal_rev1.pdf

Reference 2

http://celsiuscity.eu/wp-content/uploads/2019/11/Aarhus-Tilst.pdf

Number 43