Type

LTDH

Short description

LTDH utilizing ground heat pump for passive houses heating

Location

Østre Hageby, Stavanger

Country

Norway

End users

Passive house project with 66 dwellings, consisting of both apartment blocks and terraced houses

Heat source

Ground

Description

Ground HP that feeds network

Cooling

Missing info

Heat source-network connection

HP

Booster HP or no for SH

No

Booster HP, IHEU or DHSU for DHW

IHEU

TES

Vertical ground HEX (boreholes 200 m depth)

Centralized/ Decentralized TES

Centralized

Category

1.1.2.1.1.

Tsupply,min [°C] (network)

50

Tsupply,max [°C] (network)

55

Treturn [°C] (network)

32.5

Reference 1

https://www.danskfjernvarme.dk/-/media/danskfjernvarme/gronenergi/projekter/eudp-lavtemperatur-fjv/guidelines-for-LTDH inal_rev1.pdf

Reference 2

http://celsiuscity.eu/wp-content/uploads/2019/11/Stavanger-%C3%98stre-Hageby.pdf

Number 44